Baixe 220558812 - John - Grainger - Author - Jr - William - Stevenson - Author - Power - System - Analysis - Solution - Manual e outras Manuais, Projetos, Pesquisas em PDF para Engenharia Elétrica, somente na Docsity! Chap 1 Problem Solutions
1.1 [fev — 141 4sin(it + 30º) V and é = 11.81 cos(wt — 30º) A. find for each (a)
the maximum value, (b) the rms value and (c) the phasor expression ir polar
. . to s Ds .
and rectangular form if voltage is the 'Teferençe* Is the circuit inductive or
º capacitive? no .
Ss ;
T- IH 4 Sm (E soda e
co , 2 “
Solution: = (4,4 Cos (ustt3E KO) - |
- ” (a) Maximum values ico -Çe
Vmaz = 1414 V Imar = HI A
(b) rms values: 4
141.4 11.31
Vi= DD = 100V l=-"= =8A —
vi= = |
(c) Phasor expressions in polar and rectangular form:
v = 100,25 100+;0V
Quito 1 = 8Mf-a-joa
The circuit is inlogúive as I legs V. +30
lecas
1.2 If the circuit of Prob. 1.1 consists of a purely resistive and a purely reactive
element, find R and X, (a) if the elements are in series and (b) if the elements
are in parallel, e à Y
a MAC —
Solution: Z2= FA º R
(a) Elements in series: €, ça gem a e Ô E
7 - oo, o pos
Sade aro . . “8
R = 680 Xt = 5868 O SG 3
6,89 A
(b) Elements in parallel: N
= G de 1 - ez Ot
808780" "="0-04+—s0-0603
Y = 5=eez=8=
TE 27 Rox 42698
. plo xe = R = “ade "q = GQ)
nie: Rtg> “ass 26 (a yemaral)
1.3 In a single-phase circuit V, = 120745º V and vu = 100,-15º V with respect
to a reference node o. Find Vie in polar form.
H
Solution:
Via = Vio-Vo
Voa = 100,2-15º — 120,745º = 96,59 — 925.88 — (84.85 +;84.85)
11.74 = 110.73 = 111.357-83.95º V
2
1.4 A single-phase ac voltage of 240 V is applied to a series circuit whose impedance
is 10/60º O. Find R, X, P, Q and the power factor of the circuit.
Solution:
R = Wecos60 = 50 9
X = 1sin60º = 866 O
240,0º
= É = mp-ç0
, 10,60 — 24-80 A
P = (24)x5 = 2880 W
Q = (24) x8.66 = 4988 var
pf = cos (tan) = 0.50
or cos (tan! F) = 0.50
1.5 If a capacitor is connected in parallel with the circuit of Prob. 1.4 and if this
capacitor supplies 1250 var, find the P and Q supplied by the 240-V source,
and find the resultant power factor.
Solution:
P = 2880 W
Q = 4988-1250 = 3738 var
3738
= 10008) O
pf. = cos (tan a) 0.61
1.6 A single-phase inductive load draws 10 MW at 0.6 power factor lagging. Draw
the power triangle and determine the reactive power of a capacitor to be con-
nected in parallel with the load to raise the power factor to 0.85.
13.33
Solution:
10. q =
dg Sin (cos 06) = 13.33 a
cos-i0.85 = 31.79º
10tan31.79º = 6.2 var Ha
Q = -(1333-6.2)
= —7.13 Mvar o
|
i
|
|
|
|
|
|
|
5
(d) ja+ 02
Solution:
(aje-1 = —0.5+70.866—-1 = 1.732/7150€
(b)l-02+a = 1-(-0.5 - 50.866) — 0.5+ 90.866 = 1+51.732 = 2,00,60º
(c)a+a+j = —0.5-50.866-0.5+90866+31 = —1+91= 14147135
(d)jata? = 1/2102 41/240º = —0.866- 05-05-0866 = —1.366— 51.366
= 1.932,/225º
1.13 Three identical impedances of 10/—15º 9) are Y-connected to balanced three-
phase line voltages of 208 V. Specify all the line and phase voltages and the
currents as phasors in polar form with Vo as reference for a phase sequence of
abe.
Solution:
Van = 1202210º V Vap = 208/240º V
Voa = 120/90 V Voc = 208/120º V
Vea = 120/-30º V Va = 208/00 V
O Van 120/2100; =o
h= Sea 2285 A
O Vim 120/90 o
1, = Zoo 12,105º A
O Va 120/5300 + o
L= = 5 - lzmi5 A
1.14 alatrced-three-phase system the Y-connected impedances are 10730º O.
e KH Ve = 4167 SO V; specify Tm in polar form.
A nm
vem
Solution:
416
Gy
Va = 240/-60º V
la = e = 2M,-90º A
A .
G
—s Ven = 246 (768º
——
me as —6&” “
To Na ZitCS = 24 (MA
E E
6
1.15 The terminals of a three-phase supply are labeled a, b and c. Between any
ã pair a voltmeter measures 115 V. A resistor of 100 12 and a capacitor of 100 Q
H at the frequency of the supply are connected in series from a to b with the
3 resistor connected to a. The point of connection of the elements to each other
is labeled n. Determine graphically the voltmeter reading between c and n if
phase sequence is abc and if phase sequence is acô.
Solution:
Sequence a-b-c
115
o
ke = 116sin60º = 996 V
meter reading = 57.5+996 = 157.1] V
nk = = 575 V
9
Sequence a-c-b
E Fe = 99.
nk 7
meter reading = 99,
H
e
i 1.16 Determine the current drawn from a three-phase 440-V line by a three-phase
H 15-hp motor operating at full ioad, 90% efficiency and 80% power factor lagging.
Find the values of P and Q drawn from the line.
Solution:
15 x 746
= OLD = 29.39 A
ui V3 x 440 x 0.9x 0.8
V3x 440 x 20.39 x 0.8 = 12,431 W drawn from line
V3 x 440 x 20.39 x 0.6
V
h
O
]
9,324 var drawn from line
1.17
1.18
1.19
7
H the impendance of each of the thres lines connecting the motor of Prob. 1.16
toa bus is 0.3 + j1.0 9), find the line-to-line voltage at the bus which supplies
440 V at the motor.
Solution:
I = 20.39(0.8- 40.6) = 16.31 — j12.23 A
When the reference is voltage to neutral of the motor at the terminal where J is calculated,
or 440/V3 = 254/05 V, the supply bus voltage to neutral is
254 + 30 + (0.3 + 91.0)(16.31 — 712.23)
Line-to-line voltage |V| = v3 [271.1 +912.64]
271.1+512.64
470 V
A balanced-A load consisting of pure resistances of 15 $) per phase is in par-
alle! with a balanced-Y load having phase impedances of 8 + 56 92. Identical
impedances of 2 + j5 $2 are in each of the three lines connecting the combined
loads to a 110-V three-phase supply. Find the current drawn from the supply
and line voltage at the combined loads.
Solution:
Convert A to equivalent Y having 15/3 = 5 9/phase
5(8+76) — 40+530 13-56 7004350
5+8+76 — 18+76 13-96 * 205
341+70.732 = 349/121º Q
Current drawn at supply:
Z = 2+75+341+30.73 = 54149573 = 7.88/46.65º Q
110/v3
Hi = ca — 806 A from supply
Letting V; equal voltage at the load, line-to-line voltage:
V = 806x349 = 28.13 Vto neutral
Linetoline > = v3x2813 = 4872 V
A three-phase load draws 250 kW at a power factor of 0.707 lagging from a
440-V line. In parallel with this load is a three-phase capacitor bank which
draws 60 kVA, Find the total current and resultant power factor.
Solution:
Letting S; and 5, represent the load and capacitor bank, respectively,
Si = 25047250
10
Solution:
Per-unit base calculations:
(0.44)? x 1000
Base Z = 3 = 9.68 per unit
R = Sã = 0.031 per unit
X = E = 0.1033 per unit
Basel = oa = 26.24 A
[= e = 0.777 per unit
Voltage calculations:
V = 10+0.777(08 — 50.6) (0.031 + 50.1033)
= 10+0.777 x 0.10797 36.43º
= 10+0.0674+50.0498 = 1068672.97º per unit
lVzL] = 1.0686x440 = 470 V
1.25 Write the two nodal admittance equations, similar to Egs. (1.57) and (1.58), for
the voltages at nodes (2) and (2) of the circuit of Fig. 1.23. Then arrange the
nodal admittance equations for ali four independent nodes of Fig. 1.23 into the
Vous form of Eq. (1.61).
Solution:
dsO V-VKh+HM-VDN+M-V)Y = 0
ds O o UGHM-MDE+M-Wr = 1
Rearranging equations for bus (2) and bus (3) yields
bus OD NR +HV(K+HNAY)- MANY =0
bs o VN -KLAV(G+HYA+4Y) =
The Yous form is
D 2 g a
D [MW +r+Y) =—Ya —. —Y Y 0
2 —Ya G+R+Y) -—h -Y. hl|.|o
9 -Y. —% C+H+Y) o nl ix
9 —Yr -— 0 Cry +49] | y k
1.26 The values for the parameters of Fig. 1.23 are given in per unit as follows:
Ya=-708 Y=-740 V=-780 “jo Y=-450
Y=-;25 Y=-;08 h6=10 (90º 1 =0.68/-135º
OO
11
Substituting these values in the eguations determined in Prob. 1.25, compute
the voltages at the nodes of Fig. 1.23. Numerically determine the corresponding
Ztus matrix.
Solution:
Using the Ypus solution of Problem 1.25, substitute the given admittance values:
45 580 j40 925][W o
jo -HTO 440 350 [| Vo | 0
jo 40 -j88 50 vw |T| 10,-98º
525 550 30 983] [Vs 0687-135
Compute voltages:
YesV = I
Vous Y us V Vous 1
jOTI8T j0.6688 30.0307 70.619
ao = 1506688 707045 50.6242 50.6258
where You = Zu = | 06307 07045 306840 30.5660
506194 06258 70.660 50.6840
Vo Yos
Wu jO.TIBT 406688 30.6307 j0.6194 o
vw | — | 506688 07045 506242 50.6258 0
vw | * | 906307 07045 40.6840 0.5660 1.0,-90º
Va 506194 406258 30.5660 50.6840 | | 0.68,-135º
Vi 0.9285 — 30.2978 0.97502-17.78º
v | | 09251-503009 | — | 0.9728/-1802º
w| = |osse2-gozo | * | og ,iõeo
Va 0.8949 — 50.3289 0.9534, —20.18º
Chapter 2 Problem Solutions
2.1 A single-phase transformer rated 7.2 KVA, 1.2kV/120 V has a primary wind-
ing of 800 turns. Determine (a) the turns ratio and the number of turns in
the secondary winding, (b) the currents carried by the two windings when the
transformer delivers its rated kVA at rated voltages. Hence, verify Eq. (2.7).
Solution:
(a)
Mo Mn 12x168º
Mo Wo Tao
NM 80
Therefore, No =
EE 5200 Page lofl
To: ee5200-|8 mtu.edu
Subject: sign convention, conjugate, cosine reference
Glad to see this kind of exchange on the e-mail list,
that is what | have been hoping for.
Some comments that could help with the Ch.1 review problems:
1) As I mentioned in the first lecture when we discussed
Euler's identity, it is standard practice to define phasors
according to the cosine (real) component and this is termed
"cosine reference." Therefore, when converting from time domain
to phasor domain, we must first convert all sinusoidal functions to
equivalent cos functions. By sketching out a sine and a cosine
function, it becomes clear that a sine is just a cosine that has
been delayed by 90º. Therefore, sin(wt) = cos(wt -90º) or
cos(wt) = sin(wt + 90º).
2) The negative sign associated with | is most likely due
to how | is defined on the circuit, i.e. the assumed reference
direction of current flow that is marked on the circuit.
3) To correctly calculate complex power consumed by (or flowing in to) a
circuit element, Sin = VI” = P + jQ, where V and | have
reference polarity/direction according to passive sign convention.
4) Careful with conjugates: remember that the conjugate of a complex number
has the same magnitude, but the sign of its angle is changed. For
example, ifl = 10/30º A, then |* = 10/-30º A. Thus, negating a complex
number is not the same as taking its conjugate.
Thanks for the comments on the Ch.1 problems, | will try to go thru
these and then issue any corrections that may be required.
Looks like we are off to a good start, good to be thinking about these
details and doing some review/refreshing.
Dr. Mork
Printed for Bruce Mork <bamork Gmtu.edu> 9/9/2003
EE 5200 Page2of2
and figure it out.
Any more points of uncertainty or possible errors? Please go ahead and
start the discussion here, hopefully this is helpful.
See you all in class tomorrow morning, we will go through some more
per unit things.
Dr Mork
Printed for Bruce Mork <bamork Emtu.edu> 9/9/2003
EE 5200
To: ee5200-10mtu.edu
Subject: Chapter one problem 1.7
At 12:02 PM 9/3/2008 -0500, you wrote:
1.7: | believe that they drew the correct conclusion about the efficiency
but for the wrong reason. Anybody care to comment?
The authors rationalization seems to be sound:
Adding shunt capacitors (shunt compensation) reduces the
inductive component of the current being drawn from the
mains, i.e. flowing down the line, thus reducing the net
current flowing in the line. This reduces the |"2 R
line losses. The current flowing into the motor, however,
is unchanged (assuming the capacitor placement has not
changed the terminal voltage).
This is essentially a power factor correction situation, no
internal changes have been made to the motor, it is still
operating in the same way and with the same efficiency.
Since efficiency is related only to real power P, the Q
that is produced by the caps has no effect on motor
efficiency.
There are some devices, in cyclic loading applications,
that increase overall motor efficiency by reducing the source
voltage to the motor when the mechanical load on the motor
is removed/reduced, and then restores full voltage when the
motor is loaded down again. Not restoring full voltage, or
operating a loaded induction motor at reduced voltage
will draw excessive current, resulting in a very low efficiency
and extreme I/2 R heating of the armature windings, thus buming
itout. One basic type of motor protection is thus to trip the motor
off line if the voltage is too low and/or the current is too high,
and/or if the winding temperature gets too high.
Dr. Mork
Printed for Bruce Mork <bamork Gmtu.edu>
Page lofl
9/9/2003
11
Substituting these values in the equations determined in Prob. 1.25, compute
the voltages at the nodes of Fig. 1.23. Numerically determine the corresponding
Zipus Matrix.
Solution:
Using the Ypus Solution of Problem 1.25, substitute the given admittance values:
-jj4s j80 440 $25 Vu 0
j80 —fT0 40 350 VW lo 0
j40 j40 -;88 30 Y 1.07-90º
25 45D 30 383 Va 0.68,-135º
Compute voltages:
YesV = 1
Vas bus Y Yu TI
jOTIB7 $0.6688 70.6307 506194
ao = 506688 J0.7045 0.6042 30.6258
where Yous = Zous = | 06307 50.7045 306840 30.5660
06194 06258 0.5660 50.6840
V= Yo
Y j0.7187 506688 40.6307 30.6194 o
Y . 506688 40.7045 30.6242 j0.6258 o
Va - 50.6307 30.7045 30.6840 30.5660 1.07-90º
Va 40.6194 0.6258 50.5660 30.6840 0.682—135º
Yi 0.9285 — 50.2978 0.9750,—17,78º
Y a 0.9251 —;0.3009 | — | 0972871802
Va E 0.9562 — 40.272] * | 0.9941,-15.89º
Va 0.8949 — 50.3289 0.9534,--20.18º
Chapter 2 Problem Solutions
2.1 A single-phase transformer rated 7.2 kVA, 1.2kV/120 V has a primary wind-
ing of 800 turns. Determine (a) the turns ratio and the number of turns in
the secondary winding, (b) the currents carried by the two windings when the
transformer delivers its rated KVA at rated voltages. Hence, verify Eq. (2.7).
Solution:
(a)
Mo MN L2xiêo
Moo wo CID o
Mi 80
Therefore, No = = —
erefore, No 10 10
14
Solution:
(a) From Eq. (2.22) and (2.23),
[4] = alt! Bol[h] = omo[48 65 1[%]
so? [ TES 3.003 ] [ h ]
3.393 1.885
(b) From Eq. (2.25).
[8] = [8 EE)
- suo Sa 435 )14]
to (1)
[ioioe ] = 100008 [ 738 ]n
hence A = 0.295,2-90º A
A = mio v
(ii)
[ade] = tooxacoe| 2 )r
hence Vi = 117.30/0º V
h 1.11,-90º A
2.5 Forthe pair of mutually coupled coils shown in F ig. 2.4, develop an equivalent-T
network in the form of Fig. 2.5. Use the parameter values given in Prob. 2.4
and assume that the turns ratio a equals 2. What are the values of the leakage
Feactances of the windings and the magnetizing susceptance of the coupled coils?
Solution:
li = Ly-ely =19-2x09H=01H
Lo Loa-Lioja = 05-2x09/2 H = 005 E
Ly = 4x06H=02H
Im = alo) =2x09H=18H
w = 1207 rad/sec
iss iss Eh
Leakage reactances: = 3770
15
2 = Tá O
5.4 =
mw = SÊ o = 88 q
. . E E
Magnetizing susceptance: Bm = wlm | 1207 XLE 5
= 1474 x10? 5
2.6 A single-phase transformer rated 1.2 kV /120 V, 7.2 kVA has the following wind-
ing parameters: 7, = 0,8 9,17, = 1.2 92,1, = 0.01 Nand x, = 0.01 9. Deter-
mine
(a) the combined winding resistance and leakage reactance referred to the pri-
mary side, as shown in Fig. 2.8,
(b) the values of the combined parameters referred to the secondary side
(c) the voltage regulation of the transformer when it is delivering 7.5 kVA to
a load at 120 V and 0.8 power factor lagging.
Solution:
(a) With turns ratio a = 1.2 x 103/120 = 10,
Rj = m+otr = 0:8+100x001 9 = 18 Q
X = mteiz = 12+100x001 0 = 220
(b)
R, 2 Ri/0? = 18/10 2 = 0018 Q
X & Xe = 22/1000 = 0022 Q
Z,
à R 5X E
e IA DAN po
te) mes
m = (18+922) Q +
7200 o -
Le = |S9/Valz-8 = “150 (038.8) A = 60,-36.9º A -
I .
ha = EE =60,-369º A ”
aVopr = 1200 V
Vim = ab +hoeZo
16
4
1200 +60/-36.9 (184722) V = 1216 57/0198 V
120 V
W.ri/a = 121.66 V
(121.66 — 120) /120 = 1.38 %
IFo.rc]
H
Box]
% Regulation
“
2.7 A single-phase transformer is rated 440/220 V. 5.0 EVA. When the low-voltage
side is short circuited and 35 V js applied to the high-voltage side, rated current
flows in the windings and the power input is 100 W. Find the resistance and
Teactance of the high- and low-voltage windings if the power loss and ratio of
Teactance to resistance is the same in both windings.
Solution:
Rated /
22.73 A (low voltage)
Za9 = 11.36 A (high voltage)
2 = 3 & 308 N(RZ,X high-voltage)
X = 3082-0.7742 = 298 Q ã - 28 = 385
For equal loss in high- and low-voltage windings,
77
High voltage:r = e = 0.887 Q
5 = 385x0387 = 149 Q
2
Low voltage: r = 0.387x (3) = 0097 Q
220)?
= 149[) «0
z 14 (8) 0.373 9
2.8 A single-phase transformer rated 1.2 kV (120 V, 7.2 KVA yields the follówing
test results:
Open-Cireuit Test (Primary Open)
Voltage V> = 120 V; Current L = 1.2 A; Power W, = 40 W
Short-Circuit Test (Secondary Shorted)
Voltage Vi = 20 V; Current = 604: Power W = 36 W
19
Output = 120x63245x0.8W = 607157 W
6071.57
aorrs7 sao, ao — 8700 %
120 x 63.245 VA = 7.589 kVA
mar
Corresponding KVA level
2.10 A single-phase system similar to that shown in Fig. 2.10 has two transformers
A-B and B-C connected by a line B feeding a load at the receiving end C. The
ratings and parameter values of the components are
Transformer 4-B: 500 V/1.5 kV, 9.6 kVA, leakage reactance = 5%
Transformer B-C: 1.2 kV/120 V, 7.2 EVA, leakage reactance = 4%
Line B: series impedance = (0.5 + 93.0) Q
Load €: 120 V, 6 kVA at 0.8 power factor lagging
(a) Determine the value of the load impedance in ohms and the actual ohmic
impedances of the two transformers referred to both their primary and
secondary sides.
(b) Choosing 1.2 kV as the voltage base for circuit B and 10 KVA as the
systemwide KVA base, express all system impedances in per unit.
(c) What value of sending-end voltage corresponds to the given loading condi-
tions?
Solution:
(e) Ohmic impedances
2
Transformer A-B Primary: FE x 40.05 = 1.302 Q
152 x 108 .
Secondary: FEx 10 x 70.05 = ;11.719 Q
2 6
Transformer B-C Primary: ea xj004 = j80 Q
2
Secondary: =p x 40.04 = ;0.08 Q
vp 2
Load: fa 26 = Es cestos = 24,369º 9 :
cs
y
(b) Impedance bases E
!
o 1.22 x 108 Na
Circuit B: 0x Io = 144 Q
2
Circuit €: 120 = 144 0
10 x 103
20
Per unit impedances on new bases:
“11.719
“as
8
“ias
(15+730)
144
24 .
Load: Tag (88
Transformer A-B: = 30.08138 per unit
Transformer B-C;
40.0556 per unit
Line B:
H
9.0104 + 50.0208 per unit
H
1.667736.9º per unit
(e) Sending-end voltage calculations
sE 0.0104 + j 0.0208
j 008138 100556
—
(0.0104 +; 0.15778) pu
1.567 .369º pa
Ve = 120V = 10 per unit
1.667736.9º + (0.0104 + 20.15778) .
= 1. = 1.06
Vs 10x 166773695 1.0642 per unit
The sending-end voltage base is
Vobae = x12xHº = 400 V
500
15x 103
Therefore, the required sending-end voltage is
Vo = 400x 10642 = 425.69 V
2.11 À balanced A-connecied resistive load of 8000 KW is connected to the low-
voltage, A-connected side of a Y-A transformer rated 10,000 kVA, 138/13.8 kV.
Find the load resistance in ohms in each phase as measured from line to neutral
on the high-voltage side of the transformer. Neglect transformer impedance and
assume rated voltage is applied to the transformer primary.
Solution:
8,000
Bino) = 2 = 3347 À
Vinel = Ja xi
R 138,000/v3 = 2380 9
33.47
2.12 Solve Prob. 2.11 if the same resistances are reconnected in Y.
Solution:
Tfthe A-connected resistors are Teconnected in Y, then the resistance to neutral will be three
times as great and
R = 3x2380 = 7140 Q
21
2.13 Three transformers. each rated 5 kVA, 220 V on the secondary side, are conected
A-A and have been supplying a balanced 15 kW purely resistive load at 220 V.
A change is made which reduces the load to 10 KW, still purely resistive and
balanced. Someone suggests that, with two-thirds of the load, one transformer
can be removed and the'system can be operated open-A. Balanced three-phase
voltages will still be supplied to the load since two of the line voltages (and thus
also the third) will be unchanged.
To investigate further the suggestion
(a) Find each of the line currents (magnitude and angle) with the 10 KW load
and the transformer between a and c removed. (Assume V5, = 22070º V,
sequence q bc.)
(b) Find the kilovoltamperes supplied by each of the remaining transformers.
(c) What restriction must be placed on the load for open-A operation with
these transformers?
(d) Think about why the individual transformer kilovoltampere values include
a Q component when the load is purely resistive.
Solution:
a
+
1,
R R
n
R
b —
Aro nn
——
(a) Vas and Vs. remain the same after removing the third transformer, so Vi, is also the
same and we have a three-phase supply, and these voltages are: Vap = 220/0º V, Voo =
2207 240º V and Voa = 2207 120º V. Then, Van = 1272-30º V, Vin = 127/210º V and
Ven = 1277890º V. The line currents are
10,000
= SD 430º = 26.24/-30º
é v3 x 220 A
h = 2624/210º A
L = 2624/90 A
(b) KVAsupplica = 220 x 26.24 x 103 = 5.772 KVA
(c) The load must be reduced to (5.0/5.772) x 100 = 86.6% or 4.33 KW for each transformer.
(d) The current and voltage in each of the remaining two transformers are not in phase.
Output of each transformer before the reduction in load is,
S4 = Valj = 220/0º x 2624/30" = 5000 +72886 VA
Sa = Volj = 220/60º x 26.24/270º = 5000 - ;2886 VA
| 24
Solution:
i
! (a) Y-Y connection:
i
i
1MTRvI nov
| = 12x100xv3 V 1X 13x 3EVA
Wal = 120/83 V
2
12003 - r r
Rj = 5x = 500 9 , .
1º ( 1205 ) a R R
2
(1.23) x 108
Z = taxas 08 o
X, = 005 perunit = 200x0050 = 10 9
Z; = (500+310) Q
(b) Y-A connection: Lata rizov
1% 12x 3 EVA
Vil = 1200xv3 V coma
Val = 120 V r rm
2
na 120003) a R R
Rj = = (mê) = 1500 Q
X, = 10 8 from part (a) =
Z, = (1500+710) 9
(c) A-Y connection: 12ev ops v
1X T2XIKVA
Vizl = 1200 V — vn
[Val = 1203 V r
1200 42 500
Rj = 5x(D>—=) = >> = 18667 0 q R' R
r (558) 3
12002
2 = qaxsrie — 6880 =
X, = 005 perunit = 66.67x0.059 = 3.33 Q
Zi = (16667+7333) Q
(8) A-A connection: 1x a viva
|Vzil = 1200 V gd ——S
Mil = 120 r r
. 120032. a R R
Rj = 5x E) = 500 Q
X = 333 9 from part (c) =
Zi = (50043333) Q
2.17 Figure 2.174 shows a three-phase generator supplying a load through a three-
phase transformer rated 12 KVA/600 V Y, 600 kVA. The transformer has per-
phase leakage reactance of 10%. The line-to-line voltage and the line current at
25
the generator terminais are 11.9 kV and 20 À, respectively. The power factor
seen by the generator is 0.8 lagging and the phase sequence of supply is ABC.
(a) Determine the line current and the line-to-line voltage at the load, and the
per-phase (equivalent-Y) impedance of the load.
(b) Using the line-to-neutral voltage Vá at the transformer primary as refer-
ence, draw complete per-phase phasor diagrams of all voltages and currents.
Show the correct phase relations between primary and secondary quanti-
ties.
(c) Compute the real and reactive power supplied by the generator and con-
sumed by the load.
Solution:
(a)
Voltage ratio =
Current ratio =
Xo=
LetVs =
Then, !s =
Il =
vi =
w =
Line voltage at the load
Line current at the load
Load im-pedance - Zr
x w h
mA » »
4 dE da
a:l
2x1 e
a= o CS = 20/80
= = 0.057.308
12x 1087
fai x01 = 240 9
o E Rv = 687 EV
Hj = 20,-36.9º A
lja” = 20x20/-369º - 30º A = 400,-66.9º A
Ve jXils = 68770º— (Fes) kV
6.503,-3.34º KV
6.593, 3.340
Vija = ese = - o
Tia 50, 506 kV 329.65/-33.34º V
vBlMl=5n V
Hrl = 400 4
Vil = 329.65,—-33.34
400,568.9º
= 0.824/836º Q
H
k
e ed rmontenane eqre
26
6)
ref, ref
3a Vs =6.87kV 36.9º
.593 KV 30º
E
VL=329.65V Is=h'=204
; h =400 A
!
(c) Pg + 305 from the generator is 3VsT5, where
IV) = 3x6.87/0ºx20/36.0º KVA = 412.2/36.9º KVA
| = 329.8 kW+ 247.3 kvar
Í
Pr +5Q1 by the load is 3VL I7, where
=. 3x 329:65/-33.34º x 4007 66.9º
3VL Is Dr E
1000
329.7 kW + 5218.7 kvar
kVA = 395.67 33.56º kVA
2.18 Solve Prob. 2.17 with phase sequence ACB.
Solution:
(a) Final answers remain the same except for the following intermediate results:
a = 20/-30º 1/a* = 0.057-30º
Il = Ia = 400,/-360º 1300 A = 400,-6.9º A
VL = Vija=32965,/-334+30ºV = 32065/067º V
6)
Vi = 329.65 V
ao ref zef,
+.
ar Vç= 6.87 EV
Vi = 6.593 kV
v=6.585 L =400A
(c) Same results as in Problem 2.17.
2.19 A single-phase transformer rated 30 KVA, 1200/120 V is connected as an auto-
transformer to supply 1320 V from a 1200 V bus.
(a) Draw a diagram of the transformer connections showing the polarity marks
on the windings and directions chosen as positive for current in each wind-
ing so that the currents will be in phase.
29
and into bus (3 thru Xs,
P+5Q = 4h = 0.289+ 50.167 per unit
03
0.
h = 0.577-50.333-(-301) = 0.577 50.233
h = 0.289-50.167+(-50.1) = 0.289 — 50.267
Into bus (& thru X,
o
(b) AV =003; La=
= —j01
ta
to:
P+5Q = 0.577 470.233 per unit
and into bus (&) thru Xa,
P+5Q = 0.2894 50.267 per unit
(e)
AV = 102210 = 0.99944+500349-10 = —0.0006 + 50.0349
—0.0006 + ;0.0349 .
= DTL = 0116+70002
Loire 703 +3
h = 0577-0333 - (0.116+4 50.002) = 0.461 — 50.235
Jo = 0.289-50.167+0.116+4 40.002 = 0.405 — 50.165
Into bus (3) thru X;,
P+5Q = WIº = 0.461 +70335 per unit
and into bus (3) thru Xs,
P+5Q = WI" = 0.405430.165 per unit
Note: Compare P and Q found in parts (b) and (c) with part (a).
2.22 Two reactances X, = 0.08 and X> = 0.12 per unit are in parallel between two
buses (2) and (3%) in a power system. If V, = 1.05/10º and V, = 1.020º per unit,
what should be the turns ratio of the regulating transformer to be inserted in
series with X> at bus (&) so that no vars flow into bus (2) from the branch whose
reactance is X,? Use the circulating-current method, and neglect the reactance
of the regulating transformer. P and Q of the load and V, remain constant.
Solution:
In reactance X,,
1.05210º — 1.0 1.034 + 50.1823 - 1.0
Io = 008 DO J008 = 2.279 — 50.425
To eliminate vars to bus (3) thru X;, we need in the Xo branch
Jabeiro = —j0.425
AV .
gergi - 4
a-1 = AV = -50.425(70.08 + 70.12) = 0.0850
a
1.085 turns ratio
“YAM eve = (201/66) 03 peop sonpay
ro -S To a SM
SOL = a 0g0'T TO
VAR 65 = sexgrxrero = Iºs]
VAW FO = sexotxesgo = Ilsl
vero = legrof—serol = |" - “Il
Qom eeso = Lrrrof—20r0) = [mp4
A 3€ el aro - (SLOAEEOLOL: sus
1 13€ : 9g0'0
Av
“9s00q apnyuBem %9'g UNA
sovol-esro = (gal-go)FÉ = q
Til
se
sogrot-z0r0 = (gol-go = 1
(go: sds 1 I
“Proj VAN-SE UMA sjueimo
“YAN S0g=SEx(Z4T/SI) 03 peo] sonpol soar) pue 'pepeojrao si 7 WUN
ES9T0+SLST'O
VAW CL = cex = E,
AR g SESTO Fesl
EE9TO + LST O
= ex Sal = |
VAN gui £ SESTO Psi
mun sed cego = (sr/eg)x1go = “x
Mun rd c;sTO = (02/sg)x600 = Ix
“aseq USsoYo au) 03 SurgIsatos
4 :uoLynjoS
“UIqOId SIW9 IO] ÁIOJIBISIYES SI PORjOUI
qUSimo-SuryemoIr au, “opis aBeIjoA-MO] Sy3 UO AX Z'ET VA SE JO sseq € asn)
“SIQULIOJSUBI) SU PBO[ISAO OU [LM WollMa prol [8]09 sy] JO saradureyjoreaur
UIMUIIXEU SU) pue peol [240] VAIX S£ [eulfio ag) J0J IullojsueI? qoea jo qnd
-Mmo sxodureyjoseSou at) pur “dey AX SIT SW) UO Suprema ota “7 IouLIoysUeI
O] PaledUIOS IULIOJSURI) JE) JO 9pIs SSLIOA-MO| 9UY PIEMO3 SBEYOA UI 9500q i
Y9E RB O AY LIT IP PES dE T JoULIOJsWeI) UO são) SUJ 3] "PopeopsaMo st
ISULIOJSUBI) IOUMSU TEU OS poartury aq 1SNUI Pro [ej01 SU) YIIMA 09 saladureyos
-eSoUI SW) PUB 'ISULIOJSUBI) ovo JO Indiano aladureajoseSsur auy 'IouLojsueI
Uva WBNOLYI MUM Iod UI JUSLITO au) Jo opngufem oq3 purg gum sed 400 =X
Uma VAIX CI poYel st 7 IouojsueI) pre gum Jd 600 = X qu VAN OE
peyei st | JouLIojsucIT, SuiBBe] IOjoey Lomod 90 Ye AX ZEI VA CE Jo pro
e 4tddns 09 famered us axezado AY Va SI/ASII PaYel WpPra SIDULIOJSUBI) OM] EZ'T
0s
PE
31
Chapter 3 Problem Solutions
3.1 Determine the highest speed at which two generators mounted on the same
shaft can be driven so that the freguency of one generator is 60 Hz and the
frequency of the other is 25 Hz. How many poles does each machine have?
Solution:
Let P = number of poles:
2x60x60 2x60x25
speed = Po = Px
Po (80
Ps 3
Peo and Pos must be even integral numbers lowest value where Psy = 2.4Pos. Thus,
Pos =10 Pro = 24
3.2 The three-phase synchronous generator described in Example 3.1 is operated
at 3600 rpm and supplies a unity power factor load. If the terminal voltage of
the machine is 22 kV and the field current is 2500 A, determine the line current
and the total power consumption of the load.
Solution:
Using the values in the solution of Example 3.1,
45855
Cota = 3855 * 2500 V = 20869.1 V
Given:
Vir = 22kV
Van = (V2/V3)x 22000 V = 179629 V
H ua — 17062.9 coswt, then ia = ia mus COS WÊ and
e = 17962.9cosut -- 4.1484 x 1072 x 1207 X ia nus SÍNwt
= 17962.9coswt — 15639 is... Sin wt
Cata = 17962924 (15639500,,)) = 20869.1 V
Hence, lou = 152594 A
Li = ioualV2 = I079KA
Po = v3x22x10.79x1MW = 411.2 MW
3.3 A three-phase round-rotor synchronous generator has negligible armature re-
sistance and a synchronous reactance Xg of 1.65 per unit. The machine is
connected directly to an infinite bus of voltage 1.070º per unit. Find the in-
ternal voltage E; of the machine when it delivers a current of (a) 1.07230º per
34
3.5 A three-phase round-rotor synchronous generator, rated 16 KV and 200 MVA,
has neghgible losses and synchronous reactance of 1.65 per unit. It is operated
on an infinite bus having a voltage of 15 kV. The internal emf E; and the
power angle ô of the machine are found to be 24 kV (line-to-line) and 27.4º,
respectively.
(a)
(d)
(c)
Determine the line current and the three-phase real and reactive power
being delivered to the system.
If the mechanical power input and the field current of the generator are
now changed so that the line current of the machine is reduced by 25% at
the power factor of (a), find the new internal emf E; and the power angle
õ.
While delivering the reduced line current of (b), the mechanical power
input and the excitation are further adjusted so that the machine operates
at unity power factor at its terminals. Calculate the new values of E; and
ô.
Solution:
(a)
(66)
Using 16 kV, 200 MVA base;
V. = 15/16 per unit = 0.9375 per unit
E/6 = E 274º per unit = 1.5/27.4º per unit
E6-VizO = LX/90º —8
152274º -0.0375,0º = 1,x165/900-0
1/9008 = 0.4818/60.27º per unit
Tas-8 = 0.4818,-29.73º per unit
200 x 102
Basel = 2" KA = T27KA
aee v3 x 16
Thereiore, 1 = 048]8x7T.217KA = 3477 KA
S = 0.9375x0.4818 per unit = 0.4517 per unit
= 90.34 MVA
Thus, P = 90.34c0529.73º MW = 78.45 MW
Q = 90.34sin29.73º Mvar = 44.80 Mvar
New L, = 0.75 x 0.4818 per unit = 0.3614 per unit
90-68 = 60.27º
EiL6 = Viz0C+LX90 -8
H
0.937570º +0.3614 x 1.65260927º = 1.337/92.8º per unit
= 214/2928 kV LL
New ly = 0.3614 per unit 8 = 0
E/6 = 0.9375/0º+40.3614 x 1.65/90º
1111/32.5º per unit = 17.87/32,5º kV
3.6 The three-phase synchronous generator of Prob. 3.5 is operated on an infinite
bus of voltage 15 kV and delivers 100 MVA at 0.8 power factor lagging.
(a) Determine the internal voltage E;, power angle é and the line current of
the machine.
(b) Ifthe field current of the machine is reduced by 10%, while the mechanical
power input to the machine is maintained constant, determine the new
value of ô and the reactive power delivered to the system.
(c) The prime mover power is next adjusted without changing the excitation
so that the machine delivers zero reactive power to the system. Determine
the new power angle é and the real power being delivered to the system.
(d) What is the maximum reactive power that the machine can deliver if the
level of excitation is maintained as in (b) and (c)?
Draw a phasor diagram for the operation of the machine in cases (2), (b) and ;
(o).
Solution:
(a) From Prob. 3.5,
Valor Vi) = 0.9375 per unit
5 = 05perunit Xa = 1.65 per unit 6 = -369º
k = S/V; = 0.5/0.9375 per unit
EL6 = Vi +1Xa 90 +08
0.5
= 0,9375720 + ————= x 1.65 º — 36.9º i
520º + Toa * 1.65, 90º — 36.9º per unit
= 16258/25.7º perunit = 26.0/25.7º kV
36
New E; = 09x 1.6258 per unit = 1.46322 per unit
P = 05x0.8perunit = 0.4 per unit
. PXa Co 0,4 x 1.65
= [PÃO dn 1f o MáXibo 10 o
é =sn (E) sn (rs tasm) 28.76
V
New Q = S*(Ecos6-V)
. Xa
= am (1.46322 cos 28.76º — 0.9375)
= 0.196 per unit = 39.2 Mvar
(e) When Q=0,
Y 0.9375
= Aa = = 50.15º
5 = sig cs e) 50.15
EV. 0.0375 x 1.46322 :
= —— >DDw—— 0.15º t
P a sinó 65 sin 5 per uni
= 0.638 per unit = 127.65 MW
(d) For V., E; and Xg fixed, Qmez occurs when é = 0º. Hence,
V. 0.9375 - .
Qmos = X (E-Vi) = 65 (1.46322 — 0.9375) per unit
= 0.2787 per unit = 59.74 Mvar
E=1.626 pu.
V4=0.9375 pu.
3.7 Starting with Eq. (3.31), modify Ea. (3.38) to show that
IK .
P = esq lBI(Reos6 + Xesmô) — MIR)
[Ml
Q E+5 (Xa (IE;| cosó — |Vil) — RIEilsin 6)
when the synchronous generator has non-zero armature resistance R.
Lobo, r
—1.0057
39
257705 —1.57135
—1.57135 —1,57135 3.1427
He
257705 —1.0057 —1,57135
mH
Ley
H
cos (—180º)
HD
iabe
Withiy=4kA and Ly, = 433.6569 mH,
Los cos dy
Los = Ms | cos(8s — 120º)
cos (fg — 240º)
cos6oº 15.8475
31.695 | cos(—60º) mH = 15.8475 | mH
81.695
ia sin (30º) 10
tb = 20000 | sin (—90º) A= -20 | kA
te sin (—210º) 10
As Loo Lab Loc Loy ia
A | | Lo Lo Lie Ly io
Xe Loo Lob Le Ley te
As Lia Ly Le Ly ir
257705 —1.0057 —157135 15.8475 10
o | —10057 257705 157135 15.8475 - | er
O | 157185 -1.57135 31427 —31.6050 10
15.8475 158475 816950 433.6569 4
93.5610
—13.9215
= | 96305 | WbT
1258.2026
(b) When 6; = 60º,
1 1 1 1 2
5 3-1 Wo q Á -vê
P = 2 v3 vê o = 1 4 0
3,7 2 vw
e 1 1 1 1 1
2 2 A vã 3 va
Aa wo -y5 93.5610 97.5381
A, = F— o —13.9215 | = | 760016 | Wb-T
do » 3 —79.6395 0
mma re”
Ê dade
ia a a 10 -12.2474
al=1%-k olj-0|= 21.2182 | KA
: 1 1
io ao a E] 20 o
Il TDl——
P dade
te)
La = Lo+M,+4Lm = 4.71405mH
40
Lo = Li+M,- iLm = 3.58275mH
VEM, = 388188mH
Xe = Lyig+VEMiy = 471405 x (—12.2474)+ 38.8183x4 WbT
= 97.538] WbT
A = Lig = 3.58275x 212132 WbT = 76.0016 WbT
ão = Loio = O (sinceig=0)
My = VEMpis+Leyiy = 38.8183 x (—12.2474) + 433.6569 x 4 Wb-T
= 1259.20 WbT
3.10 The armature of a three-phase salient-pole generator carries the currents
ia = V2x 1000sin(8a— 84) À
2 x 1000sin (84 — 120º — 84) A
V2 x 1000sin (8; — 240º — 6.) A
%&
te
(a) Using the P-Transformation matrix of Eq. (3.42), find the direct-axis cur-
Tent iy and the quadrature-axis current iq. What is the zero-sequence cur-
rent io?
(b) Suppose that the armature currents are
2x 1000sin (a — 84) A
v=%w=0
H
ia
Determine is, à, and io.
Solution:
(a)
ig ia
iq = Pli
ig te
' i ja sin (8a — 6)
- 3/8 -43 o | x 10002 | sin(, — 0, — 120º) | A
*% & > sin (84 — 6, — 240º)
sin (8a — 8, — 60º)
10003 | sin (84 — 04 +30º) | À
h
0
41
(5)
ia 5 à + + sin(0; — 05)
ia = V3 g -38 o | x 10002 o A
i + LA o
* ã sa
sin (8a — 8.)
20
- 4 sin(64—-0,) | À
1
va sin (Ba — 8)
3.11 Calculate the direct-axis synchronous reactance Xa, the direct-axis transient
reactance X4 and the direct-axis subtransient reactance X4 of the 60 Hz salient-
pole synchronous machine with the following parameters:
L, = 2.7656 mH Lys = 433.6569 mH Lp = 4.2898 mH
M, = 1.3828 mH M,= 31.6950 mH Mp = 3.1523 mH
Lm = 0.377] mH M,= 37.0281 mH
Solution:
La = EL+M-— Sm = 2.7656+ 1.3828 5 x 0.377imH = 4.71405 mH
Xa = 1207 x471405x 1030 = 17779
a 3Mjo . 3 369500 o
Lã = la-5 Tg — AT1405 5 x asa MH = 12303 mH
X4 = 1207 x1.2393x 109 = 04879
W-L- M$Lp + MBLe, — 2MyMbM,
4a — “ca Lolp-M
= andas o (Ses x 4.2898 + 3.15232 x 433.6569 — 2 x 31.6950 x 3.1523 x 37.0281 nE
2 4336569 x 4.2808 — 3702817 '
= 09748 mH
X& 1207 x 0.9748 x 10290 = 0.367 Q
3.12 The single-line diagram of an unloaded power system is shown in Fig. 3.22.
Reactances of the two sections of transmission line are shown on the diagram.
The generators and transformers are rated as follows:
44
(a) Draw the impedance diagram for the power system. Mark impedances in
per unit. Neglect resistance and use à base of 50 MVA, 138 kV in the 40-0
line.
(b) Suppose that the system is unloaded and that the voltage throughout the
system is 1.0 per unit on bases chosen in part (a). Ifa three-phase short cir-
cuit occurs from bus C'to ground, find the phasor value of the short-circuit
current (in amperes) if each generator is represented by its subtransient
reactance.
(c) Find the megavoltamperes supplied by each synchronous machine under
the conditions of part (b).
Solution:
(a)
Base voltages are:
409 lines 138kV
2089 lines 138kKV
Gen. 1&2 20XkV
Motor 3 13.8 kV
. . 138?
Base impedance in lines = = 381 9
40
40 9 line: = = =0. H
ine: Z 381 0.105 per unit
R 20 .
W9Mline:Z = CET 0.053 per unit
Transformers:
5
YY = 01x 5. 0.250 per unit
20
' 50
YA = 01x T- 0.333 per unit
Gens. 14 2:
183250
X" = 020x (5) x % = 0.405 per unit
45
Motor 3: 50
X" = 020x FT = 0.833 per unit
(b) Ifa fault occurs at C, by symmetry equal currents are input from generators 1 and 2.
Moreover, no current should exist between busses Á and B through the j0.105 per unit
branch. If this branch is omitted from the circuit, the system simplifies to
SH
E, = E, = E, = 1070 per unit
X = X = 0.405+0.25040.053 40.333 per unit = 1.041 per unit
Xas = 0.333 per unit
o “E] e :
5] = lh] = TT Toa per unit = 0.9606 per unit
lb] = E = sm per unit = 3.0 per unit
Hj = 49212 per unit
50 x 108
J LC = DDD A =W9BA
case É V5x 138 x 10º
Hj = 4922x20018A = 1029KA
(e)
IS = [89] = 10x 50x 0.9606 MVA = 48.03 MVA
Sa) = 10x50x30MVA = 150 MVA
Chapter 4 Problem Solutions
4.1 The all-atumintm conductor identified by the code word Bluebell is composed
of 37 strands ekch having a diameter of 0.1672 in. Tables of characteristics
of all-aluminum conductors list an area of 1,033,500 emil for this conductor
(1 cmil = (r/4)x 107º in?). Are these values consistent with each other? Find
the overall areal of the strands in square millimeters.
Solution:
diameter = 0.1672x 1000 = 167.2 mils/strand
45
Motor 3: 50
X" = 0.20x 3 = 0.333 per unit
(b) Ifa fault occurs at C, by symmetry equal currents are input ffom generators 1 and 2
Moreover, no current should exist between busses 4 and B through Lhe 70.105 per unit
branch. If this branch is omitted from the circuit, the system simplifies tO
3x L
E) c
k
O SH
E, = E, = E = 1.070 per unit
X = Xbo= 0.405 + 0.250 + 0.053 + 0.333 per unit = 1.041 per unit
Xs = 0.333 per unit
o El 10 eo .
&l = lhl= E = Tó per unit = 0.9606 per unit
IEis] 1.0 . .
= 2 = t = 30
135] Dol Ta per uni 3.0 per unit
Hj] = 48222 per unit
50 x 108
h tC = SDDD—— À = 291.8 A
case d Vê x 13.8 x 10º
gl = 49212x 2091.8 A = 10.29 KA
Sil [So = 10x 50x 0.0606 MVA = 48.03 MVA
Ss = 10x50x30 MVA = 150 MVA
Chapter 4 Problem Solutions
4.1 The all-aluminum conductor identified by the code word Bluebell is composed
of 37 strands each having a diameter of 0.1672 in. Tables of characteristics
of allaluminum conductors list an area of 1,033,500 emil for this conductor
(1 emil = (7/4) x 10º in?). Are these values consistent with each other? Find
the overall area of the strands in square millimeters.
Solution:
diameter = 0.1672x 1000 = 167.2 mils/strand
48
where, for example, D,a denotes the distance in meters between conductors
a and d.
(b) Hence compute the mutual inductance per kilometer between the power
line and the telephone line.
(c) Find the 60 Hz voltage per kilometer induced in the telephone line when
the power line carries 150 A.
oe
Solution:
(a) Let circuit a-b carry the current 1, so that
l=-h=IA(andi=i=0)
since 3) 1 = O for the group, Eq. (4.36) remains valid.
= 2x1077 ——
Xe x (rem; Do » Z th 5)
Therefore,
x = 2x 107 xIn Dee Wi-t/m
oc
Similarly,
- Dia
A = 2x 1077
é Das
Aca (linkage of the loop) is given by
DicDas
Aok = 2x1077 e Da.
e — Ag x x ln DacDs
Mutuai Inductance = xin DicDaa
DacDoa
= H/m
Die = /(125-052 4182? = 195m
Dad (1.25+0.5)2 41.82 = 25im
E
49
Flux linkages with e-d:
— 5 Note that flux through
due to do Goa = 2x 10 lniis e-d due to 1, is
dueto lb de = —2x 10-"I in fl Ê
opposite that due to Jp
Note also that J, and 1, are 180º out of phase. So, due to 1, and 4,
2.51
Pa = 4x107"1 nto
2.51
= "Ino = dl 0
M 4x 107“In TOS 101x1 H/m
(e) Via =wMI=877x101x10-7 x 10º x 150=5.71] V/km
4.7 If the power line and the telephone line described in Prob. 4.6 are in the same
horizontal plane and the distance between the nearest conductors of the two
lines is 18 m, use the result of Prob. 4.6(a) to find the mutual inductance
between the power and telephone circuits. Also find the 60 Hz voltage per
kilometer induced in the telephone line when 150 A flows in the power line.
Solution:
o o o o
| 25 | 18 | 1 |
| sm | m (tm |
215
dueto Ja da = 2x10K Insos
dueto Db da = —2x101 nã since bh = La
, - 215x 18 7
dueto I and h da = 2x10 ns = —0,01288 x 107" 1,
M = Se - oorsBx10* H/m
ha
Va = wMI = 377x150M x 10º = 0.0728 V/km
4.8 Find the GMR cf a three-strand conductor in terms of 7 of an individual strand.
Solution: Given this bundie: &
GMR = (0.779 x2rx2r)) = rYAx 0770 = 146r
4.9 Find the GMR cf each of the unconventional conductors shown in Fig. 4.15 in
terms of the radius r of an individual strand.
Solution:
(a) Bundie: BB
50
cMR = “or [(2 x2x 22) sl" = 1.72%r
(b) Bundle: &
2
cMR = 0779)! (2 x 2x 23) (2x2x2)r2 = "VERONA x 3/18 = 169%
(c) Bundle: Goo
GMR = (0.779) x Br? x Br? x ar? = 1.704r
(d) Bundie: (O,
3 3
GMR = Virirx W(4x4x2x2x2V3) (24x 2,3) 130
rx2x342 x 07798 = 2.20
4.10 The distance between conductors of a single-phase line is 10 ft. Each of its
conductors is composed of six strands symmetrically placed around one center
strand so that there are seven equal strands. The diameter of each strand is
0.1 in. Show that D, of each conductor is 2.177 times the radius of each strand.
Find the inductance of the line in mH/mile.
Solution: ;
Outside conductors are counter-clockwise numbered 1 through 6. The center conductor is
number 7. Each radius is r and the distances between conductors are:
Do = %W Du = 4r
Ds = Dik -Dã = 2rv3
DD = Wr)(DEDLDaD (2) = x N/(2r2 x 3x 2r2 x Dr? x Dr x DE
ETTA,
UVB) or
vV6
o ct 10x12 o ,
L = 4x10h ZIF x 00 * 1000 x 1609 = 4.51 mH/mi
4.11 Solve Example 4.2 for the case where side Y of the single-phase line is identical
to side X and the two sides are 9 m apart as shown in Fig. 4.9.
53
4.18 For short transmission lines if resistance is neglected the maximum power wkich
can be transmitted per phase is equal to
[Vel x [Val
1]
where Vs and Va are the line-to-neutral voltages at the sending and receiving
ends of the line and X is the inductive reactance of the line. This relationship
will become apparent in the study of Chap. 6. If the magnitudes of Vs and Va are
held constant and if the cost of a conductor is proportional to its cross-sectional
area, find the conductor in Table A.3 which has the maximum power-handling
capacity per cost of conductor at a given geometric mean spacing.
Note to Instructor: The purpose of this problem is to stimulate the
student's examination of Table A.3 and is worthwhile in introducing
class discussion of conductor selection.
Solution:
Power transmission capability per conductor cost if resistance is neglected is |Vs]|Vai/(X 4)
based on our cost assumption where A is the cross-sectiona! area of the conductor. There
fore, the product X - 4 must be minimized. Assuming De is fixed, examining the Table
shows that in comparing any two conductors the percent difference in À is much greater than
that of X. So, A is the controlling factor, and Partridge or Wazuwing would be selected.
However, resistance cannot be neglected. A “conduetor must be large enough in cross sec-
tion that melt-down caused by |I[2R loss will not occur under the most extreme operating
conditions. The reference (Aluminum Electrical Conductor Handbook) gives information on
thermal effects. If reaciance causes too high a voltage drop on a line, double-circuit lines or
bundied conductors must be provided. The reference (Analytical Development of Loadability
Characteristics for EHV and UHV Transmission Lines) contains information on maximum
transmission capability of lines.
4.19 A three-phase underground distribution line is operated at 23 KV. The three
conductors are insulated with 0.5 cm solid black polyethylene insulation and lie
fiat, side by side, directly next to each other in a dirt trench. The conductor
is circular in cross section and has 33 strands of aluminum. The diameter of
the condutor is 1.46 cm. The manufacturer gives the GMR as 0.561 em and
the cross section of the conductor as 1.267 cm?. The thermal rating of the line
buried in normal soil whose maximum temperature is 30º C is 350 A. Find the
de and ac resistance at 50º C and the inductive reactance in ohms per kilometer.
To decide whether to consider skin effect in calculating resistance determine the
percent skin effect at 50º C in the ACSR conductor of size nearest that of the
underground conductor. Note that the series impedance of the distribution line
is dominated by R rather than X; because of the very low inductance due to
the close spacing of the conductors.
A
54
4.20
Note to Instructor: When assigning this problem, it may be advisable
to outline part of the procedure.
Solution:
Rev de 228 +50
o. lis
Roo, de 228 +20
o plo 283x 1008
Roca = T= Tori — 0228 0/km
Rsoc de = 1,121x0.223 = 0.250 0/km
Skin effect can be estimated from the values in Table A.3. The area 1.267 cm? is
2
1.267 x (53) x í x 10º = 250,000 cmils
Wezwing has an area of 266,800 cmils and for this conductor
Rsos ac 0.388
Foo 00046 x 5.28
= 1123
Since temperature rise would account for a factor of 1.121, skin effect is only about 0.2%. With
insulation thichness of 0.5 em center-to-center conductor spacing is 2 x 0.05 +1.46 = 2.46 cm.
So,
Dea = VZ40x246x2x 246 = 3.099
Xr = 87 x100x2x107"m cs = 0.129 0/km
The single-phase power line of Prob. 4.6 is replaced by a three-phase line on
a horizontal crossarm in the same position as that cf the original single-phase
line. Spacing of the conductors of the power line is Dis = 2Di2 = 2D»a, and
equivalent equilateral spacing is 3 m. The telephone line remains in the position
described in Prob. 4.6. If the current in the power line is 150 A, find the voltage
per kilometer induced in the telephone line. Discuss the phase relation of the
induced voltage with respect to the power-line current.
Solution:
YDxDx2D = “2 =3
= = = 238m
[— s28m —
o o Os—
1.8m
55
The center conductor of the 3-phase line causes no flux linkages with d-e since the conductor
is at an equal distance from d and e.
De = De = YRA4(238-0.5) = 2.60m
De = Da = (/182+(238+05/ = 340m
1, 340
dueto Ja, da = 2x10 E]
1,340
dueto Jo, Que = 2x10 into
3.40
Total flux linkages = 2x10"(L-h)n 500
Since Jp lags Ja by 120º,
OS
V3 La 4,30%
= 3.40 E W
due = 2x10 V3loln 55230 Wim
M = 929x 19º H/m
V = uMx15 = 37x 10x 9.29x 150x1000 = 5.25V/km
e
t
&
1
The induced voltage leads 1, by 90º + 30º = 120º; that is, V is in phase with Z..
4.21 A 60-Hz three-phase line composed of one ACSR. Bluejay conductor per phase
has fiat horizontal spacing of 1! m between adjacent conductors. Compare
the inductive reactance in ohms per kilometer per phase of this line with that
of a line using a two-conductor bundle of ACSR 26/7 conductors having the
same total cross-sectional area of aluminum as the single-conductor line and
11 m spacing measured from the center of the bundies. The spacing between
conductors in the bundile is 40 em.
Solution:
De = Vilx1]1x22 = 13.86m
Bluejay:
D, = 00415(254x12x102) = 00126m
13.86
X = -" 3 qe = 0
2x107 x 10 x37in gia = 0.528 0/km
DR» 00... Md
57
5.2 The 60-Hz capacitive reactance to neutra! of a solid conductor, which is one
conductor of a single-phase line with 5 ft spacing , is 196.1 K9-mi. What value
of reactance would be specified in a table listing the capacitive reactance in
ohrn-miles to neutral of the conductor at 1-ft spacing for 25 Hz? What is the
cross-sectional area of the conductor in circular mils?
Solution:
At 5ft spacing,
Xo = 2965x10t mó = 196,10 2 mi
m> = 6614
7 = 000870 ft, or 0.0805 in
= (2x 0.0805 x 1000)? = 25, 992 circ mils
From Eq. (5.12), at 1-ft spácing and 25 Hz,
1779 1
25 0.00870
c=
x 108in = 356,200 2 mi
5.3 Solve Example 5.1 for 50 Hz operation and 10 ft spacing.
Solution:
1.779 x 108 10
Xe = O om O mi = 02115 MO mi
Bo = Lam usmi
Xe
O .
Xi = 59 X0.1074 MO mi
8
Xi = 59X 00683 MO mi
X = SS (01074 + 0.0688) MO mi = 0.2109 MO -mi
Bo = 4742 uS/mi
i
:
5.4 Using Eq. (5.23), determine the capacitance to neutral (in uF/km) of a three-
phase line with three Cardinal ACSR conductors equilaterally spaced 20 ft
apart. What is the charging current of the line (in A/km) at 60 Hz and 100 kV
line to line?
Solution:
For Cardinal conductors,
p= 1196 (1
"2 "2
27 x 8.85 x 10-12
' G = ESSO pm=ogx102 Fjm = 9.276x 10 uF/km
2
t In qrróesar
58
100 x 10?
lag = 27x60x9.276x 107º x A
A/km = 0.202 A/km
5.5 À three-phase 60-Hz transmission line has its conductors arranged in a triangu-
lar formation so that two of the distances between conductors are 25 ft and the
third is 42 ft. The conductors are ACSR Osprey. Determine the capacitance to
neutral in microfarads per mile and the capacitive reactance to neutral in ohm-
miles. If the line is 150 mi long, find the capacitance to neutral and capacitive
Teactance of the line.
Solution:
Osprey diam. = 0.879in
Da = VBxbx4 = 2972f
27 x 8.85 x 10712
€ = mma Fim
n(667%9)/2
= 8301x 102 F/m = 8.301 x 108 x 1.609 uF/m = 0.01336 uF/mi
108
= = —— = 0. 8 Q.mi
Xe = 37x ODISH 0.1985 x 10º Q -mi
From Table A.3, X/ = 0.0981. Interpolation from Table A .4 yields X4 = 0.0999+0.72(0.1013—
0.0999) = 0.1006. From Table 4.4, Xc = 0.1987 x 108 9. mi,
For 150 miles,
Cr = 150x0.01336 = 2.004 yF
0.1987
—-— 0º = 5 Q
XKc EO xl 132:
5.6 À three-phase 60-Hz line has flat horizontal spacing. The conductors have an
outside diameter of 3.28 cm with 12 m between conductors. Determine the
capacitive reactance to neutral in ohm-meters and the capacitive reactance of
the line in ohms if its length is 125 mi.
Solution:
De ViZx13x24 = 1512m
Tr = 00328/2 = 00164
X = 2.862 x 10% 15.12
= 3.95 Bo.
& dora — 3.256 x 10º OQ -m
For 125 miles,
3.256 x 10º
Xe = ax165 — 16198
5.7 (a) Derive an equation for the capacitance to neutral in farads per meter of
a single-phase line, taking into account the effect of ground. Use the same
nomenclature as in the equation derived for the capacitance of a three-phase
E
59
line where the effect of ground is represented by image charges.
(b) Using the derived equation, calculate the capacitance to neutral in farads
per meter of a single-phase line composed of two solid circular conductors each
having a diameter of 0.229 in. The conductors are 10 ft apart and 25 ft above
ground. Compare the result with the value obtained by applying Eg. (3.10).
Solution:
Do —+
O -m
Fio due to
eonnnllo nn image
charges
—Ja & To
(a) Due to charges on a, b:
Due to image charges:
- Fiz H,
Va = 4 ln ape + ga ln q
Due to image and actual charges:
2 G% hp Do Et) q Do Ho
o» = Bk nã Da Pora
27k
Cn = 2Coh = 7 EinEg Fm
z
(6) By Eq. (5.10),
5 12
C = 2x x8.85x 10 = 7.996 x 10-12 F/m
10x 12
In (dez)
And from part (a) above,
2x x 8.85 x 10-12
tn (BA) — Im (E)
5.8 Solve Prob. 5.6 while taking account of the effect of ground. Assume that the
conductors are horizontally placed 20 m above ground.
Cn = = 8018x 102 F/m
62
In original positions in the transposition cycle,
Vis TI = 1a43t
distance a-b' vVIg5285 = 31.75
distance aa” = v252+282? = 37.54 ft
Dê, = Dp = 41443 x3175) = 21046
De = V2x2B = 2646 ft
Dea = VU042x2646 = 27 k
;
D, = [(vomrixarsa)' voosa=m]" = riste
22.71
distance a-b
H
= — = 5. 7
L=ox0inds = 5688x107H/m
= 5.963 x 1077 x 10º x 1609 = 0.959 mH/mi
XL = 377x0.959x 10? = 0.362 0/mi/phase
(6) r = EB = 0.0462 ft asin part (a) above, except that 7 is substituted for D,:
Do = [(VOMBIxIT3A) VODAD= =]! = 1282 R
From part (a) above, Deq = 22.71 ft and
Xc = 2965x10-tn o = 85,225 Q-mi/phase to neutral
Lg = iss o0o 8 = 0.935 A/mi/phase = 0.467 A/mi/conductor
;
Chapter 6 Problem Solutions
6.1 An 18-km 60-Hz single circuit three-phase line is composed of Partridge conduc-
tors equilaterally spaced with 1.6 m between centers. The line delivers 2500 kW
at 11 kV to a balanced load. Assume a wire temperature of 50ºC.
(a) Determine the per-phase series impedance of the line.
(b) What must be the sending-end voltage when the power factor is
(:) 80% lagging (ii) unity (iii) 90% leading?
(c) Determine the percent regulation of the line at the above power factors.
(d) Draw phasor diagrams depicting the operation of the line in each case.
Solution:
(a)
18
0.37
3792 x Tao
0.465 9/mi
R
From Table A.3, X,
= 42420
"
ss
62
in original positions in the transposition cycle,
distance ab = 1424352 = 1443ft
distance ab” = v142+2852 = 3175 f
distancea-a” = 252428? = 37.54 ft
Dk = Di = Viá4xaris = 2n04k
De = 422x28 = 2646f
Dea = V21042x2646 = 2271 R
D. = [vans X 3754)" VOONAIx | = 1152f
L = ox nda = 5.602 x 107 H/m
= 5.963x 107? x 10º x 1609 = 0.959 mH/mi
X = 37x0959x 10º = 0,362 0/mi/phase
Es O)r = 5 = 0.0462 ft asin part (a) above, except that r is substituted for Ds:
Do = [(VEDaa Xa754)" VOA BJ* = 12804
From part (a) above, Deq = 22.71 ft and
22n
Xe = 2.965x10“h Tm — 85, 225 2. mi/phase to neutral
Long Tb orol vê = 0.935 A/mi/phase = 0.467 A/mi/conductor
Chapter 6 Problem Solutions
6.1 An 18-km 60-Hz single circuit three-phase line is composed of Partridge condue-
tors equilaterally spaced with 1.6 m between centers. The line delivers 2500 KW
at 11 kV to a balanced load. Assume a wire temperature of 50ºC.
(a) Determine the per-phase series impedance of the line,
tb) What must be the sending-end voltage when the power factor is
(i) 80% lagging (ii) unity (iii) 90% leading?
(c) Determine the percent regulation of the line at the above power factors.
(d) Draw phasor diagrams depicting the operation of the line in each case.
Solution:
(a)
18
0.3792
3792 x T60s
0.465 9/mi
R
From Table 4.3, X,
= 4.242 0
"
63
and since 1.6 m = (1.6 x 100)/(2.54 x 12) = 5.25 £t,
Xa = 0.2012 (Table A 4,53”)
X = 0465402012 = 0.666 9/mi
Forl8km, X = UBx7
0.666
Es = 7410
Z = 4MP+jTAS = 857/6035 0
(b) For power factor = 1.0,
1, = 20 11,000
R = x
= 1812 A
1 v3
= 6350 V
Vs = 6350+131.2(4.04 + 97.451)
6906 + 3977.6 = 69757 8.06º
sending-end line voltage = V3Vs = v3x6975 = 12,081 V
For power factor = 0.8 lagging,
Hal =
Vs =
sending-end line voltage =
For power factor = 0.9 leading,
Hal =
Vs =
sending-end line voltage =
% Regulation
at pf.=0.8 lagging, % Reg.
at unity pf., % Reg.
at pf =0.9 leading, % Reg.
(d) For pf.=0.8 lagging,
2500
V3x11x0.8
6350 + 164/-36.87º x 8.577 60,88º
7639 475.60 = 7660/4.19º
V3Vs = V3x7660 = 13,268 V
= 164 A
2500
V3x11x09
6350 + 145.8/25,84º x 8.57760.85º
6433 +j1247 = 6553710.97º
V3Vs = V3x 6553 = 11,350 V
= M58A
[sl = Vel
= = x 100%
[Val .
7660 — 6350
=> ——D——— O!
mo X 100%
6975 — 6350
- 00%
6553 — 6350
6350
20.63%
9.84%
h
x 100% 3.20%
k
ciano indo
66
Solution:
80 9
600 2 1000 9
1000
= 1.08VrR+ 80
Va 1.08VR + 807r
Ig = Teto 0
= 0.0028Vp + 1133Fp
V;
Vo = VR+ (1a+ vo) x80 = Va +80/p+0.08VR
= 0.001VR + 0.0018VR + Ir + 0.133/r
The ABCD constants are 4
B
108 CC =
800 D= 1133
6.4 The ABCD constants of a three-phase transmission line are
A=Da=gÕ936+70016 = õ0.936/0.98º
B = 335+j188 = 142/7640 0
C=(-518+7914)x10? gs
The load at the receiving end is 50 MW at 220 kV with a power factor of
0.9 lagging. Find the magnitude of the sending-end voltage and the voltage
regulation. Assume the magnitude of the sending-end voltage remains constant.
Solution:
50, 000
la = SD 25848 = 1458/-25.84º À
* = VEx 2x0 És e
220, 000
VR = = 127,0
R V3 127,00070º V
Vs = 0.936/0.98º x 127,00070º + 1427 764º x 145.8,--25.84º
= 118,855+ 52033 + 13,153 + 915,990 = 133.23/7.77º kV
With line-to-line sending-end voltage [Vs] = V3 x 133.23 ='230.8 kV,
230.8 .
Veni = ag = 2465kV
246.5 — 220
% Reg. o x 100 = 120%
6.5 A 70 mi, single-circuit, three-phase line composed of Ostrich conductors is ar-
ranged in flat horizontal spacing with 15 ft between adjacent conductors. The
line delivers a load of 60 MW at 230 kV with 0.8 power factor lagging.
68
6.6
6.7
Qs = 1.086x0.742 xsin(2.125º —(-36.54º)) = 0.503 per unit
100 x 0.503 = 50.3 Mvar
A = 1+ A = 1+ 5 (0.1166767.5º x 0.192/90º) = 0.990, 0,248º
[Vel /LAl> [Va re]
[Va gil
(1.086/0.980) — 1.0
= DL xz10% = 97%3%
10
x 100%
A single-circuit, three-phase transmission line is composed of Parakeet con-
ductors with flat horizontal spacing of 19.85 ft between adjacent conductors.
Determine the characteristic impedance and the propagation constant of the
line at 60 Hz and 50ºC temperature.
Solution:
At 50ºC and 60 Hz, from Table 4.3, for Parakeet conductors,
r 0.1832 Q/mi Xa = 0423 Q/mi
Da = Vi9o85x2f = 25f
At 25 ft, Xo(inductive) 0.3906 N/mi
Therefore,
z = 01832+45(0.423+0.3906) 2/mi
= 0834/7731º Q/mi
Xi = 00969x 108 OQ mi
Xalcapacitive) = 0.0955x 10º Q.mi
o j 08,80%
= Zi+X T quo ,0g0 S/Mi
= 51975 x 10"8,90º S/mi
Characteristic impedance:
2. E. BAT .
Ze = v V5igsx10- SN = 400.6/-6.346º 0
Propagation constant:
v= Vzy = 4/0.834x5.1975x 10-62 77.312 +90 mi"! = 208x 1072 mi!
Using Eos. (6.23) and (6.24) show that, if the Teceiving-end of a line is ter-
minated by its characteristic impedance Z., then the impedance seen at the
sending end of the line is also Ze regardless of line length.
69
Solution:
H Za = Z.. then Ip = Vp/Zo: and Va — TaZ.=0.
Y
From Ea. (6.23) Vs Ya + InZe
Vet IaZo ns
From Ea. (6.24) Is = 2%
e
where L is the length of the line. Finally,
Z, = Vs/ls = Ze (which is independent of L)
6.8 A 200-mi transmission line has the following parameters at 60 Hz
resistance r = 0.21 Q/mi per phase í
series reactance x = 0.78 Q/mi per phase i
shunt susceptance b = 5.42 x 10º S/mi per phase :
(a) Determine the attenuation constant a, wavelength À and the velocity of
propagation of the line at 60 Hz.
(b) If the line is open circuited at the receiving end and the Teceiving-end
voltage is maintained at 100 kV line-to-line use Egs. (6.26) and (6.27) to
determine the incident and reflected components of the sending-end voltage
and current.
(c) Hence determine the sending-end voltage and current of the line.
Solution:
(a)
r = 6219/mi = = 078Q/mi
2 = (021+70.78) Q/mi = 0.808277.31º Q/mi
y = 542x 10"f277.31º S/mi
4 = VZ = 2092x 102/8247 mi!
= a+j8 =: (2.744 x 107º 4 92,074 x 107%) mir"
Atrenuation-constant a = 2.744 x 107º nepers/mi
27 2mx108
Wavel hAÃ==>=—"-=—mi = i
avelengt| 2 TOA mi 3030 mi
m 3
Velocity of propagation Af = = = REA mijs = 181770 mi/s
(6)
Characteristic impedance: Z, = 386.05,-7.53º O
72
Is = 300/-cos 09 A = 300,-25.84º À
5 cosa
Va = 0.8904/134º x 150.11 ,0º — 188.825.70.450 x 800,-25.84º |,
1000
= 108.85,-22.76º kV
Val = v3x10885kV = 188.5 kV line-to-line
Ir = -1.131x 102,90.41º x 150.11 x 1073209 + 0.8904/1.34º x 300,-25.84º A
= 3720/-48.95º A
Hal = 324
The receiving-end power factor is then
PÉ. = cos(-22.76º 448.95º) = 0.897 lagging
6.12 A 60 Hz three-phase transmission is 175 mi long. Tt has a total series impedance
of 35 + 140 9) and a shunt admittance of 930 x 1078790º S. H delivers 40 MW
at 220 kV, with 90% power factor lagging. Find the voltage at the sending end
by (a) the short-line approximation, (b) the nomial-z approximation and
(c) the long-line equation.
Solution:
1 = Ymmi
Z = 35+340 = 1443/7596º 9
Y = 930x10!s
40, 000
la = >—2>—— = 116.6,-2584º A
R V5x 220 x 0.9 deito
(a) Using the short-line approximation,
Vs = 127,017+116.6,-25.84º x 144.3/75.96º = 127,017 + 10, 788 +512,912
= 138,408/535º V
IV = 3x 138,408 = 239.73 kV
(b) Using the nominal-m approximation and Eq. (6.5),
o.1342 o
Vs = tarot ( ; 18590 +1) + 1443/7590 x 116.6,-25.,84º
= 127,017 (0.935 + 90.0163) + 10,788 + 912,912 = 129,5494 14,982
130,41276.6º
v3x 130,412 = 225.88 kV
IVsl
(c) Using the long-line equation,
144.37 75.96º * o o
Ze (sao ig esagEE Z obs ) = 884 ,-7,02
q = v144.3x930x 10-8,165.06º = 0.3663/83.0º = 0.0448 + 30.364
ObMB DIA — 1 045872086" — 097734 j0.3724
E
T8
ec OAB Ç-50.364 — 09562,-20.86º = 0.8935 — 50.3405
cosha! = (0.9773 + 70.3724 + 0.8035 — 50.3405)/2 = 0.9354 4 500160
sinhyl = (0.9773 4 70.8724 — 0.8935 + 50.3405)/2 = 0.0419+ ;0.3565
Vs = 127,017(0.9354 + 50.0160) + 116.6,-25.84º x 394, —7.02º (0.0419 + 40.3565) ”
= 118,812+92,0324 10,563+912,715 = 129,315+714, 747 :
= 130,15326,5º V
sl = v3x130,153 = 2254kV
6.13 Determine the voltage regulation for the line described in Prob. 6.12. Assume
that the sending-end voltage remains constant.
Solution:
By Problem 6.12, volt-to-neutral results,
Vs = 130.15 kV Va = 127.02kV ,
For Jr=0, Vs = Vpcosh4l,
130.15 |
Wa nel = sas eso Uia] 139.12kV
139.12 — 127.02 -
% Reg. = rm *100 = 953%
6.14 A three-phase 60-Hz transmission line is 250 mi long. The voltage at the sending É
end is 220 kV. The parameters of the line are R = 0.2 9/mi, X = 0.8 N/mi í
and Y = 5.3 uS/mi. Find the sending-end current when there is no load on the
line.
Solution:
i
Z = (02+708)x250 = 206.1/75.96º
Y = 250x5.3x 10º = 1,305x 10-2,90º '
ql = VZY = v206.1x1.325x 10-3,165.96º = 0.5226,82.08º |
0.0639 + 70.5187
206.17 75.96º
Ze = VE = ED = 394/1020
1.325 x 10-32, 900
By Eq (6.39) for Jp = 0,
inh
Il = (Vs) cod
Bl = 05187 rad = 29.72º
extçil — 0.9258+ 30.5285
ecale-i8l = 08147 50.465]
1
coshyl = 5 (0.9258 + 0.8147 4 50.5285 — 50.4651) = 0.8709/2.086º
74
sinhyl
l 0.9258 — 0.8147 + 5 (0.5285 + 0.4651)] = 0.4999,83.61º
3 Lob]
— 20,000//3 O4mmorasero o
= 3947-702 *garoo,20ge — 1850/88,54º A
6.15 If the load on the line described in Prob. 6.14 is 80 MW at 220 kV, with
unity power factor, calculate the current, voltage and power at the sending end.
Assume that the sending-end voltage is held constant and calculate the voltage
regulation of the line for the load specified above.
Solution:
220 80,000
Va= = =127kV Ir = = = 209.95 A
=] "Ex
With values of cosh! and sinhYl from Problem 64,
Vs = 127,017(0.8703 + 90.0817) + 209.95 x 394, -7.02º x 0.4999,7 83.61º
110,528 + 74,026 + 9,592 + 940,9232 = 128,014,720.23º V to neutral
4
[Vel = 3x 128,014 = 21.7kV
Is = mosstostas+so0317) + DO o o, 83.610
s — O HEsid: me 3947-7020 * 040082 88.61
= 182.72+56.66-1.77+4161.13 = 2468/4284 A
Ps = v3x2217x2468c0s (20.3º — 42.84º) = 87,486 kW (or 87.5 MW)
AtIr=0,
127,000
Dr = t
0.8709 145,826 V to neutral
145.8 — 127
127
[Vel
% Reg. = 148%
6.16 A three-phase tranmission line is 300 mi long and serves a load of 400 MVA,
0.8 lagging power factor at 345 kV. The ABCD constants of the line are
A = D=oQBI80/13
B = W22/842º O
C = 0.001933,90.4º S
(a) Determine the sending-end line-to-neutral voltage, the sending-end current
and the percent voltage drop at full load.
(6) Determine the receiving-end line-to-neutral voltage at no load, the sending-
end current at no load and the voltage regulation.
Solution:
345.000 400,000
Va = = 199,18620º V Ir = Si = 6694,-3687º À
R vã FO VEx3s
77
or, inversely proportional to X if we assume constant |Vs| and |VR|. Additionaliy,
De, = Y5x5x10 = 6.30 m, or 6.30/0.3048 = 20.67 f
(a)
211 2087
For Partridge: X = D0754in Traz = 0.5172 9/km
0 2087
For Osprey: X = 0074n a = 0.4969 0/km
Ratio of Pr (new/old):
0.5172
0.4969
1.041 (41% increase)
6)
D. = 0.0217 x (0.4/0.3048) = 0.1688 ft
20.67 :
X = 0.0754tn pas = 0.3625 N/km
0.5172
> = 1427 Ti
5675 1.427 (427% increase)
(c) Pa increases by factor of soy? = 2.78 dueto increased V. Pp decreases due to increase
of X.
Dea = VBXExD = 8807R
33.07
= 0.0754 = 0.5526
X 0.0754ln Vo; 0.5526 km
Decrease factor = fair?
— 05526
Resultant factor of increase = 2.78x O.ir2 = 2.602
0.5526
Increase = 1603%
However, in addition to the increase in conductor spacing and insulation, larger conduc-
tors wili probably be required since current wil! increase by a factor of about 230/138
and |F|2R loss in the line by a factor of about 2.78 for the increase in load at the same
power factor.
6.21 Construct a receiving-end power-circle diagram similar to Fig. 6.1) for the line
of Prob. 6.12. Locate the point corresponding to the load of Prob. 6.12 and
locate the center of circles for various values of |Vs| if |Va| = 220 kV. Draw
the circle passing through the load point. From the measured radius of the
latter circle determine |Vs] and compare this value with the values calculated
for Prob. 6.12.
78
Solution:
Use scale of 1” = 50 MVA. By comparing the work in Problem 6.12(c) with the equation
Vs = AVR + Bla we find
A = 0.9354+700160 = 0.936,0,08º
B = 394,-7.02º (0.0419+ 903565) = 141.4/76.28º Q
B-a = 76.28º -0.98º = 75.3º
(AJVRÍÊ 0.9354 x 220?
E] 141.4
Use above data to construct load line through origin at cos! 0.9 = 25.8º in the first quadrant.
Draw a vertical line at 40 MW. The load point is at the intersection of this line and the load
line. The radius of the circle through the load point is 7.05”,
705x50 = 3525
[Vel Val .
e = 8525
tB]
320.2 MVA
352.5 x 141.4
[Vs] 20
= 226.5 kV
6.22 A synchronous condenser is connected in parallel with the load described in
Prob. 6.12 to improve the overall power factor at the receiving end. The sending-
end voltage ís always adjusted so as to maintain the receiving-end voltage fixed
at 220 kV. Using the power-cirele diagram constructed for Prob. 6.21, determine
the sending-end voltage and the reactive power supplied by the synchronous
condenser when the overall power factor at the receiving end is (a) unity
(b) 0.9 leading.
Solution:
On the diagram for Problem 6.21 draw a new load line in the fourth quadrant at cos-10.9
with the horizontal axis. Draw power circles at radii [Vs||VR|/|B| = 311, 327, 342, 358, 373
and 389 MVA for |Vs| = 200, 210, 220, 230, 240 and 250 kV, respectively. This provides the
power circle diagram that we can use for paris (a) and (b).
For pf.= 1.0 read [Vs] = 214 kV at 40 MW on the horizontal axis. The vertical distance
between the horizontal axis and the load line in the first quadrant respresents the kvar of the
capacitors needed. The value is 19.3 kvar.
For p.f.= 0.9 leading, read [Vs] = 202 kV where the vertical line through 40 MW intersects
the load line in the fourth quadrant. The vertical distance between the two load lines at
40 MW represents the kvar of capacitors needed. The value is 38.6 kvar.
6.23 A series capacitor bank having a reactance of 146.6 9 is to be installed at the
midpoint of the 300-mi line of Prob. 6.16. The ABCD constants for each 150 mi
portion of line are
D = 0.9534,70,8º
90.337284,1º 9
0.001014/90.1º S
A
B
Cc
79
(a) Determine the equivalent ABCD constents of the cascade combination of
the line-capacitor-line. (See Table A.6 in the Appendix.)
(b) Solve Prob. 6.16 using these equivalent ABCD constants.
Note to Instructor: This problem is somewhat long, but the solution
is interesting to show that the ABCD constants of networks in series
as given in Table 4.6 can be calculated by matrix multiplication.
The problem also shows the large reduction in voltage accomplished
by series capacitors in the middle of the line. Compare results of
Problems 6.16 and 6.23.
Solution:
(a)
Letà = 0.953420,3º 90.33284.1º
- 0.001014790.1º 0.9584,0.3º
ã 1020º 146/-900 ) +
Ax [ 0 10,0” xA
0.953420.3º 50.91,-78.65º 0.9534/0.3º 90.33/841º
0.001014/90.1º 1.102270.27% |* 0.001014/90.1º 0.9534/0.3º
. 0.959721,18º 42.307/645º
— | 0.002084/90.4º 0.9597,1.18º
l c»D lu
(b) For Va and Ta from Problem 6.16,
Vs = 0.9597/L18º x 199, 18670 +42.30/645º x 6604/-36,87º
216,870245º
Is = 0.002084/90.4º x 199,186/0º + 0.95977 118º x 669.4 [36.87º
= 5204/4.44º
Voltage drop = pele x 100 = 8.15%
(Compare this voltage drop with that of Problem 6.16)
VanL = A6 soa | 225,977/332º V
0.95977 1.180
Isnz = 0.002084/90.4º x 225,977/332º = 470.9/987º A
225,977 — 199,186
% Reg. osso x 100 = 13.45%
(without capacitors 57.6%)
6.24 The shunt admittance of a 300-mi transmission line is
Ve = 0+356.87x 108 S/mi
ET
82
Solution:
Imagine a vertical line on the diagram of Fig. 6.15(b) at one-fourth the line length from the
sending end toward the receiving end. Intersections of this line and the siant lines occur at
T = 0.257, 1.757, 2.257, 3.757, etc. Changes in voltage occur at these times. The sum of
the incident and reflected voltages are shown between slanted lines and determine the values
Plotted below.
120V 10 v
| | LJ sv
cal 60 V :
tlm
o T 2 3 sT
6.28 Solve Example 6.8 is a resistance of 54 Q is in series with the source.
Solution:
For voltage,
- 54-30 2
* É 54300 7
= 90-30 1
ºR É ara O 2
Initial voltage impressed on line:
30
e — = 4286V
34H x 120 42.
inal value:
Final value: . 0 sv
90 + 54
poê
Po
75 V 7 v
Tha2.86 73.47 V
7 v—
2”
68 v— 54.29 v
arf-zo.4
60 v
ar f
74.34 0 T 27 37 4r 5”
6.29 Voltage from a de source is applied to an overhead transmission line by closing
a switch. The end cf the overhead line is connected to an underground cable.
Assume both the line and the cable are lossless and that the initial voltage along
the line is v*. If the characteristic impedances of the line and cable are 400 9
and 50 12, respectively, and the end of the cable is open-circuited, find in terms
of vt
A
83
(a) the voltage at the junction of the line and cable immediately after the
arrival of the incident wave and
(b) the voltage at the open end of the cable immediately after arrival of the
first voltage wave.
Solution:
(a) The initial wave of voltage vj arriving at the juction with the cable “sees” the Z, of
the cable. So, at the end of the overhead line:
50 — 400
= 0.777
50 + 400
PR =
and the voltage at the juction is
(1-0.777)v* = 022%7
which is the refracted voltage wave travelling along the cable.
(b) At the end of the cable pp = 1.0 and
vp = (0.223+0.223)0* = 044607
6.30 A de source of voltage Vs and internal resistance Rs is connected through
a switch to a lossless line having characteristic impedance R.. The line is
terminated in a resistance Ra. The travelling time of a voltage wave across the
line is 7. The switch closes at t = 0.
(a) Draw a lattice diagram showing the voltage of the line during the period
t=O0tot=7T. Indicate the voltage components in terms of Vs and the
reflection coeficients pa and ps.
(b) Determine the receiving-end voltage at t = 0, 27, 4T and 6T, and hence
att =2nT where n is any non-negatíve integer.
(c) Hence determine the steady state voltage at the receiving end of the line
in terms of Vs, Rs, Ra and R..
(d) Verify the result in Part (c) by analyzing the system as a simple de circuit
in the steady state. (Note that the line is lossless and remember how
inductances and capacitances behave as short circuits and open circuits to
de.)
Solution:
(a)
vovl — Rr-R. 2 R$-R
1= "SRA Rs PRE RAIA. “E RAR.
84
PsoBvs
o
t=0> Va(0)
t=2T >» Va(2T)
t=4T7 > Va(4T)
H
Val +Ve+orVo = (1+on)Vo
VR(2T) + pspRV; + ps ohVs
1 +pn)V; + psortl + pr)Ve
(+ or)L+ ospr)Vr
Val4T) + RVE + PORV;
++ ospr)Ve + 2oRU + pR)VE
= (1428) [L+ mer + (papa) Vi
'
t=6T > Va(6T)
Hence at any given t = 2n7T,
n-l Te
1-
ValênT) = (1+08)4 5 (soa) | Vy = (1+ 09) Tleenl y,
5=0 PsPR
(c) At the steady state, n — 00. If Rs or Ra £0, [psprl < 1 and (pspr)” — 0 as n — 00.
Hence,
V
V; = pd
'R(oo) G+pr) ID pspR
j Ra-R Rs- R
Since, pr = =
hos, PR RRTÃ, Ml = Dk
2Rp
item = Fes
10 (Rs+RM(RR+RO)
1- pspR 2R.(Rs + Ra)
R
Vo = Envy.
1 R+R f
2Rp (Rs + RJ(Rr+ Ro) Re Ra
V; = . = .
Po) = mrR O RAs cho) “Ro+A OT HRS
(d)
86
7.2 Using the Ypus modification procedure described in Sec. 7.4 and assuming no
7.3
mutual coupling between branches, modify the Ypus obtained in Prob. 7.1 to
refeci removal of the two branches DG) and (OG) from the circuit of Fig. 7.18.
Solution:
To remove branches (D-) and GQ), we add the following blocks to Ypus :
oo oo
Sliciwo Sli
This results in the following modified Y pus :
Do o ao
-;35 925 jo 50 30
js js já 0 30
jo ja -jN2 GB 30
JO 50 je -H0 52
jd JO JO jG2 28
eseso
The circuit of Fig. 7.18 has the linear graph shown in Fig. 7.19 with arrows
indicating directions assumed for the branches a to h. Disregarding all mutual
coupling between branches
(a) determine the branch-to-node incidence matrix A for the circuit with
node O as reference.
(b) find the circuit Ypus using Eq. (7.37).
Solution:
(a) The branch-to-node incidence matrix is found to be
DOS Do
Oofi-lr o oo
Ol-1 0 1 0/0
Oojoºo-1 1 00
Aa-O|/0-1 0 01
oOoto o 11/06
Dlo o o 1
Oil-1 0 0 0 0
OLo 0 o 0
87
(6) Yor is given by
o 0 ooo oo
-;25 . . . . . . :
2 . . . . Ê
=;
99090000
d
%
. : - - —j0.8
D Q 9 O o
Dl-jps 925 92 50 30
Olss 15 do 30 35
Yo = ATypA= 8] 52 ja js js 350
9| 2% 30 8 —0 32
ol so 55 j 2 -j78
7.4 Consider that only the two branches D-Q) and Q-Q) in the circuit of Fig. 7.18
are mutually coupled as indicated by the dots beside them and that their mutual
impedance is 0.15 per unit (that is, ignore the dot on branch 2-6). Determine
the circuit Ybus by the procedure described in Sec. 7.2.
Solution:
The primitive impedance matrix for the mutually coupled branches (D-(3) and OQ is in-
verted as a single entity to yield the primitive admittance matrix
=
2a DB DS
DB [E gas - [rasa Sites)
OO [5015 50.25 5146341 —j4.87805
Building blocks of the two mutually coupled branches D-) and O) are
Do 29
2 [4 “t-szanoos) 8 [4 “a nasean
DO 2 q
2 [4 “Jonas 5 E a t-samen)
Building blocks of the remaining branches are determined as
o DO 9 o
oia Slácjess Blu
o o 3 o
8 [4 “ift-sa) 2 [4 “ileso & [1)-;80)
ss
Combining all the above building blocks gives
o 2 G o o
O [-5593902 ;306M1 G097561 50 50
O | j3963841 —j1237805 341464 30 35
O | 097561 ;341464 51239025 98 30
a 30 jo 58 -nNo 32
o jo 55 50 j2 8
7.5 Solve Prob. 7.4 using Eq. (7.37). Determine the branch-to-node incidence ma-
trix A from the linear graph of Fig. 7.19 with node O as reference.
Solution:
The branch-to-node incidence matrix found in Prob. 7.3 can be used here. Ypr is obtained
by inverting Zpr as follows.
o ooo vo o”
O [504 . . . . . . .
6 505 j015
O JO 15 j025
-721.0 : a
Ypr = Zpr “o . 0.125 .
o 05
g E
O - j1.25
O O e Do vo oO
O [-525 . . . . .
O -j243902 j1.46341
O 5146341 —j4.87805
-O : 8
o . —38 .
o 2
O “jd .
O “ —308
Using Eq. (7.27), we have
D o B D o
OD [593902 ;396341 gogmse O º
O | 5396841 —j1237805 ;341464 O 55
O | jo97561 341464 —9123005 ;8 O
q 0 o 8 -pjo 2
o 0 js o 52 -j78